FUME HOOD PERFORMANCE STANDARD


Hood Used for Typical Laboratory Purposes

  • An intake face velocity of not less than 100 linear feet per minute (fpm) across an imaginary vertical plane at the hood sash with the sash 2/3 open.
  • An intake face velocity of not more than 100 linear feet per minute (fpm) with the sash full open.
  • For variable volume fume hoods, the intake face velocity shall be set at 100 feet per minute (fpm).

Hoods Used for Radioactive Isotopes

  • An intake face velocity of not less than 100 fpm with the sash 1/2 open.
  • An intake face velocity of not more than 125 fpm with the sash full open.
  • For variable volume fume hoods, the intake face velocity shall be more than 125 fpm.
Height of Opening
  • The height of the opening is measured from the hood deck for those hoods having deck level air foils.
  • The bottom of the sash should be placed even with the arrow on the Air Flow Sticker
Contacts
  • All new fume hoods are to be measured by University Risk Management & Environmental Health Safety (EH&S) prior to acceptance.
  • Hoods used for typical laboratory purposes shall be checked by the Industrial Hygiene Unit, ext. 5-3241.
  • Hoods used for radioactive isotopes shall be checked by the Radiation Safety Unit, ext 5-3781.
  • If there is a problem with a fume hood, please contact Facilities at ext. 3-4567 IMMEDIATELY



QUESTIONS? Contact EH&S Industrial Hygiene at (585) 275-3241 or e-mail EH&S Questions.